How to Use
FEATURE DETAIL
How to UseSensor for Iron and Steel Industry

Malfunction output

What is a malfunction output?

The failure output (FAULT) determines the failure of the light receiving part (receiver) as well as the light emitting part (transmitter) and outputs when one of them are failure.
* However, the waveguide type of micromaster monitors only the operation of the transmitter.

About the products with malfunction output, the indicator lights, and the output operation

Installed model Indicator light Output operation
KRG series It will light when the light emitting or receiving circuit is abnormal □ OUT4
Normal: CLOSE
Abnormal: OPEN
KAD series Projector: It will light when the amount of light emitted is 2/3 or less of the initial value
Receiver: It will falsh when the amount of light received is 1/5 or less of the initial value continuously (about 3 seconds).
□ Terminal number 9-10
Normal: CLOSE
Abnormal: OPEN
□ Terminal number 10-11
Normal: OPEN
Abnormal: CLOSE
MBX-211 Transmitter failure indicator: It will light when the light emitting circuit is abnormal
Receiver failure indicator: It will light when the light receiving circuit is abnormal
Note) If the transmitter fails at the same time, the receiver failure indicator will not light up.
□ Terminal number 9-10
Normal: OPEN
Abnormal: CLOSE
□ Terminal number 10-11
Normal: CLOSE
Abnormal: OPEN
MBX-301 Failure indicator: It will light when a transmission failure occurs. □ Terminal number 9-10
Normal: OPEN
Abnormal: CLOSE
□ Terminal number 10-11
Normal: CLOSE
Abnormal: OPEN
VMH series RUN: It will light when the internal CPU stops or runs out of control. □ RUN
Normal: CLOSE
Abnormal: OPEN
PRP series Main unit display
E1: Motor failure
E2: Shutter motor failure
E3: Sensor internal temperature abnormality
D-SUB 15 pin
□ Pin number 11-12
Normal: OPEN
Abnormal: CLOSE
□Pin number 13-14
Normal: CLOSE
Abnormal: OPEN


Terminal block
□ Terminal number 7-8
Normal: OPEN
Abnormal : CLOSE
□ Terminal number 8-9
Normal: CLOSE
Abnormal: OPEN